Learn About Voltage Drop

Understanding voltage drop calculations is essential for electrical installations

What is Voltage Drop?

Voltage drop is the reduction in voltage as electrical current flows through a conductor. Every conductor has resistance, and according to Ohm's Law (V = I × R), when current flows through this resistance, a voltage drop occurs.

This means the voltage available at the load (equipment) is less than the voltage at the source. Excessive voltage drop can cause:

  • Motors to run hot and inefficiently
  • Lights to dim
  • Electronic equipment to malfunction
  • Increased energy consumption and costs

CEC Rule 8-102 Requirements

3%

Maximum

Maximum voltage drop for any feeder or branch circuit

5%

Maximum Total

Maximum total voltage drop from service to point of utilization

The voltage drop calculation should be based on the connected load if known, otherwise 80% of the overcurrent device rating (per CEC Rule 8-102).

Voltage Drop Formulas

Single-Phase

Vd = 2 × I × L × R / 1000

Factor of 2 accounts for both conductors (line and neutral)

Three-Phase

Vd = √3 × I × L × R / 1000

√3 ≈ 1.732 is the phase factor for balanced loads

Where:

  • Vd = Voltage drop in volts
  • I = Current in amperes
  • L = One-way conductor length in meters
  • R = Conductor resistance in ohms per kilometer

Copper vs Aluminum Conductors

Copper (Cu)

  • ✓ Lower resistance (better conductivity)
  • ✓ Smaller size for same ampacity
  • ✓ More durable connections
  • ✗ Higher cost
  • ✗ Heavier weight

Aluminum (Al)

  • ✓ Lower cost
  • ✓ Lighter weight
  • ✗ Higher resistance (~1.6× copper)
  • ✗ Requires larger sizes
  • ✗ Special termination requirements

Tip: Aluminum typically requires about 2 wire sizes larger than copper for the same current-carrying capacity.

Temperature Rating Effects

RatingInsulation TypesResistanceAmpacity
60°CTW, UFLowerLower
75°CTHWN, RW75MediumMedium
90°CTHHN, RW90HigherHigher

Higher temperature ratings allow more current but also have higher resistance, resulting in more voltage drop. Most terminations are rated for 75°C.

Conductor Reference Data (CEC Tables)

SizeCu Resistance
(75°C Ω/km)
Cu Ampacity
(75°C)
Al Resistance
(75°C Ω/km)
Al Ampacity
(75°C)
#14 AWG10.720A17.4N/A
#12 AWG6.7325A1120A
#10 AWG4.2335A6.9330A
#8 AWG2.6650A4.3740A
#6 AWG1.6765A2.7550A
#4 AWG1.0585A1.7365A
#3 AWG0.833100A1.3775A
#2 AWG0.661115A1.0990A
#1 AWG0.524130A0.863100A
#1/0 AWG0.416150A0.685120A
#2/0 AWG0.33175A0.543135A
#3/0 AWG0.261200A0.431155A

Values based on CEC Tables D3 (resistance) and Tables 2/4 (ampacity for 1-3 conductors in raceway). Aluminum #14 AWG is not permitted per CEC Rule 4-002.